A physics-aware safety gateway for small water utilities. HackPrinceton Fall ‘26 · Business & Enterprise track · working name, change it if you like.

Everyone on the team (and every AI assistant you use) reads this file first. The section called The contract is the only thing all three of us depend on. Change it only after telling the other two.


1. The pitch in four sentences

In July 2026, CISA saw attackers going after more than 100 internet-exposed US water systems, mostly small towns whose pump controllers (PLCs) were reachable from the internet. CISA’s advice was to put a gateway between the internet and the PLC. Backflow is that gateway: it reads every command headed for the PLC, runs it through a physics model of the plant, and refuses anything that would overflow a tank, drain the town’s pressure, or overdose chlorine. An AI agent then investigates what happened, puts the station back in a safe state, messages the one operator on call in plain English (today on the dashboard’s phone panel; SMS is future work), and drafts the incident report.

2. How it works

 attacker / remote operator
          |
          v   Modbus TCP :1502
 +--------------------+        +---------------------------+
 |  GATEWAY (laptop)  |<------>|  PHYSICS MODEL (python)   |
 |  1 parse command   |        |  predict(state, command)  |
 |  2 policy check    |        |  -> safe? what breaks,    |
 |  3 physics check   |        |     and in how many min   |
 |  4 allow / hold    |        +---------------------------+
 +--------------------+
      | allowed only          held or odd events
      v  Modbus TCP :502            |
 +--------------------+             v
 |  STATION (ESP32)   |     +---------------------------+
 |  relay 1 = pump    |     |  AGENT (deepagents)       |
 |  relay 2 = doser   |     |  investigate -> act ->    |
 |  PIR + light =     |     |  ask operator -> report   |
 |  "someone on site" |     +---------------------------+
 |  OLED, buzzer, LEDs|             |
 +--------------------+             v
      ^                      operator's phone panel (dashboard),
      |  reads relays,       incident report (markdown)
      |  writes tank level
 +--------------------+
 |  PLANT TWIN        |  the "real world": same physics model,
 |  (laptop)          |  stepped forward in time, sped up for the demo
 +--------------------+

Two rules that keep this honest and safe

  1. The AI is never in the hot path. Allow/hold is decided by plain code (policy + physics) in milliseconds. The agent only works on what has already been held or flagged.
  2. The agent cannot send arbitrary commands to the station. Its only write tools are “revert to last known good”, “enter safe mode” and “block a source”. Releasing a held command needs the operator’s approval.

What is real and what is simulated (say this to judges; they respect it)

Real Simulated
Modbus TCP traffic, the gateway, the block Tank level and chlorine (computed by the twin)
Relays switching a pump/fan, buzzer, OLED The “town” (a potentiometer sets water demand)
On-site presence sensing (PIR, cabinet light) The PLC itself (an ESP32 stands in for it)

3. Repo layout and owners

backflow/
├── README.md              <- this file (shared)
├── shared/
│   └── registers.yaml     <- the register map, single source of truth
├── firmware/              <- EE   · ESP32 station (PlatformIO)
├── physics/               <- MechE· plant model, limits, tests
├── twin/                  <- MechE· runs the model as the "real world"
├── sim/                   <- CompE· software station (fallback if ESP32 dies)
├── gateway/               <- CompE· proxy, policy, agent, API
│   ├── proxy.py
│   ├── policy.py
│   ├── events.py
│   ├── agent/
│   └── api.py
├── dashboard/             <- CompE (MechE helps with the plant view)
├── attacks/               <- MechE· demo scripts, run only against our own rig
├── docs/
│   ├── prompts/           <- the three role prompts
│   ├── plans/             <- PLAN_COMPE.md, PLAN_EE.md, PLAN_ME.md (one per person)
│   ├── research.md        <- sources, market numbers, operator quotes
│   └── demo.md            <- demo script and judge Q&A
├── CLAUDE.md              <- rules every AI assistant loads automatically
├── .env.example
└── .gitignore

One directory per owner means almost no merge conflicts.

4. The contract

4.1 Network

Thing Address Notes
Station (ESP32) STATION_HOST:502 Modbus TCP, unit id 1
Software station 127.0.0.1:5020 same register map, used when no hardware
Gateway 0.0.0.0:1502 what “the internet” talks to
Dashboard/API localhost:8000  

Campus Wi-Fi (puvisitor) uses a sign-in page the ESP32 cannot pass, and may block device-to-device traffic. Run everything on a phone hotspot.

4.2 Register map (full version in shared/registers.yaml)

Scaling: level and temperature ×10, chlorine ×100. All values unsigned 16-bit.

Coils (read/write)

Addr Name Default Meaning
0 PUMP_CMD 0 1 = run the supply pump (relay 1)
1 DOSER_CMD 1 1 = run the chlorine doser (relay 2), only while the pump runs
2 AUTO_MODE 1 1 = station controls the pump from level setpoints
3 SAFE_MODE 0 1 = doser off, pump on local level control with default setpoints, remote writes to holding 0–4 and coils 0–2 ignored
4 ALARM 0 1 = buzzer + red LED

In AUTO_MODE and SAFE_MODE the station writes the pump/doser state it chose back into PUMP_CMD / DOSER_CMD (that is its memory between the setpoints). What the relays are actually doing is in PUMP_RUNNING / DOSER_RUNNING below. The doser never runs without the pump (no flow, no dose), matching the physics model.

Discrete inputs (read only)

Addr Name Source
0 PRESENCE PIR motion in the last 60 s
1 CABINET_OPEN photoresistor sees light
2 LOCAL_BUTTON button held (local acknowledge / manual)
3 HIGH_LEVEL_SWITCH IR obstacle module, stands in for a float switch
4 PUMP_RUNNING relay 1 is on (after auto, safe mode and the high-level interlock)
5 DOSER_RUNNING relay 2 is on (DOSER_CMD and rate > 0 and pump running and not safe mode)

Input registers (read only)

Addr Name Scale Source
0 DEMAND_PCT ×10 potentiometer, 0–100 % of max town demand
1 CABINET_TEMP_C ×10 DHT11
2 CABINET_HUMIDITY ×10 DHT11
10 LOGIC_HASH – CRC16/MODBUS (init 0xFFFF) of holding 0–4 as 10 bytes, each register big-endian
11 UPTIME_S – seconds since boot (wraps)

Holding registers (read/write)

Addr Name Scale Default Meaning
0 DOSER_RATE_PCT ×1 10 doser output, 0–100 %
1 LEVEL_HIGH_SP ×10 850 pump stops above this level
2 LEVEL_LOW_SP ×10 400 pump starts below this level
3 CHLORINE_TARGET ×100 100 1.00 mg/L
4 LOGIC_VERSION – 1 bumped when control settings change
100 TANK_LEVEL_PCT ×10 600 written by the twin only
101 CHLORINE_MGL ×100 100 written by the twin only

The twin talks to the station directly (it is “physics”, not a network user). Everything else goes through the gateway.

4.3 Physics API (physics/)

from physics import PlantState, Command, predict, step

state = PlantState(level_pct=60.0, chlorine_mgl=1.0, demand_pct=40.0,
                   pump_on=True, doser_on=True, doser_rate_pct=10,
                   level_high_sp=85.0, level_low_sp=40.0, auto_mode=True)

cmd = Command(kind="register", address=0, value=100)   # doser to max

p = predict(state, cmd, horizon_min=120)
p.safe            # False
p.violations      # [Violation(code="CHLORINE_HIGH", minutes_until=<N>,
                  #            value=4.0, limit=4.0, pre_existing=False,
                  #            message="Chlorine exceeds 4.0 mg/L in about N plant-minutes")]
p.trajectory      # [(t_min, level_pct, chlorine_mgl), ...] for the dashboard plot

next_state = step(state, dt_s=1.0)   # used by the twin

minutes_until comes from the parameters in physics/model.py; do not quote a number from this example. The twin builds its state from PUMP_RUNNING / DOSER_RUNNING with auto_mode=False, so the station (not the model) decides the pump.

Violation codes: TANK_OVERFLOW, PRESSURE_LOSS (tank too low), CHLORINE_HIGH, CHLORINE_LOW, PUMP_SHORT_CYCLE, SETPOINT_OUT_OF_RANGE. predict must be pure, fast (<20 ms) and must never raise on odd input.

4.4 Event schema (gateway -> agent, dashboard, database)

{
  "id": "evt_0042",
  "ts": "2026-11-14T03:12:09Z",
  "src_ip": "203.0.113.7",
  "function": 6,
  "kind": "register",
  "address": 0,
  "name": "DOSER_RATE_PCT",
  "old_value": 10,
  "new_value": 100,
  "decision": "HOLD",
  "reasons": ["CHLORINE_HIGH in 11 min", "source not seen before", "nobody on site"],
  "prediction": { "safe": false, "violations": [], "trajectory": [] },
  "station": { "presence": false, "cabinet_open": false, "level_pct": 61.2, "chlorine_mgl": 1.02 }
}

decision is one of ALLOW, HOLD, DENY. Held commands are not forwarded; the gateway answers the sender with a Modbus exception.

5. Demo scenarios (attacks/)

Run these only against our own ESP32 or the software station.

# Name What the script sends What should happen
0 Normal day operator turns pump on, small setpoint change allowed, relay clicks
1 Chlorine overdose DOSER_RATE_PCT -> 100, DOSER_CMD -> 1 (run after #0: with the pump off no chlorine reaches the tank) held, “chlorine > 4 mg/L in N min”
2 Drain the town AUTO_MODE -> 0, PUMP_CMD -> 0 at high demand held, “pressure loss in N min”
3 Overflow LEVEL_HIGH_SP -> 1000, PUMP_CMD -> 1 held, “tank overflows in N min”
4 Logic tamper setpoints changed behind the gateway’s back LOGIC_HASH mismatch, agent reverts
5 Operator on site same change as #1 but smaller, with PRESENCE + CABINET_OPEN agent asks operator, approval releases it

Scenario 1 is the one we show in the two-minute demo. The rest are for judge questions.

6. Working together

7. Milestones

When Milestone Proof
Fri 11pm Skeleton repo up, software station answers Modbus, predict() returns something
Sat 3am Parts work alone relay toggles over Wi-Fi; physics tests pass; proxy forwards and logs
Sat noon First block scenario 1 is held by the gateway against the software station
Sat 4pm On hardware scenario 1 held against the ESP32; relay stays off; twin drives the OLED level
Sat 8pm Hour-24 demo attack -> hold -> agent explains -> operator text -> reply -> report
Sun 2am Polish dashboard, scenarios 2–5, logic-hash check (advisory lookup: not built)
Sun 5am Freeze no new features; record 2-min video; write Devpost
Sun 7:30am Submit deadline is 8:00am; do not cut it close

If hardware fails: switch STATION_HOST to the software station. Nothing else changes.

8. Prizes we are entering

Add an integration only if it makes the product better.

9. Two-minute demo

  1. 0:00–0:20 “In July, attackers went after over 100 internet-exposed US water systems, mostly small towns with one operator and no security team. This is a pump station.”
  2. 0:20–0:45 Normal command: relay clicks, pump runs, dashboard shows ALLOW.
  3. 0:45–1:15 Attack: doser to max. No click. Dashboard shows the predicted chlorine curve crossing 4 mg/L and the reasons. Say “4 mg/L is EPA’s maximum residual level for chlorine; we use it as our alarm line” (EPA compliance is a running annual average, so never say the attack “breaks the EPA limit”).
  4. 1:15–1:40 The operator’s phone panel on the dashboard shows a plain-English message. Reply “block”. The incident report appears with a timeline.
  5. 1:40–2:00 “One box per station, sold through the integrators who install the PLCs. 81% of US water systems are small. We start with one.”

10. Open decisions


Run it

Windows (PowerShell):

python -m venv .venv
.venv\Scripts\Activate.ps1
pip install -r requirements.txt

Mac:

python3 -m venv .venv
source .venv/bin/activate
pip install -r requirements.txt

Then python tasks.py --help (sim, gateway, test, demo).